## 7.2 Back End Housing, Power, and RFI Shielding
|
|
|
We propose that the ALPACA digital beamformer back end reside
|
|
|
in the new GBO data center. We understand that this facility is still
|
|
|
under construction with an estimated completion in the next year.
|
|
|
|
|
|
Signal lines from the on-telescope front end will be over 138 optical fibers
|
|
|
(not including spares) and routed directly to the ALPACA server racks for tray
|
|
|
management and splicing. The following describes the physical infrastructure
|
|
|
needs to accommodate this back end.
|
|
|
|
|
|
### 7.2.1 Server Racks
|
|
|
The ALPACA digital back end hardware was presented and described in detail in
|
|
|
[Section 5.3](../5-dbe/5.3) and will be housed in six 44U server racks, each with
|
|
|
a footprint of 24"x41". These racks have mesh screened doors for front-to-back
|
|
|
air flow cooling, cable access openings in the top and bottom for routing from
|
|
|
and to the rack, and removable solid side panels to join multiple rack
|
|
|
enclosures together. The racks are pictured below.
|
|
|
|
|
|
<div align="center">
|
|
|
<img src="../img/dbe/alpaca-racks.png" width="700">
|
|
|
</div>
|
|
|
|
|
|
### 7.2.2 F-engine Rack Mount Enclosure
|
|
|
The enclosure for the Xilinx ZCU216 and 16-channel RX board will be a General
|
|
|
Devices utility chassis, item number CHA-05-21.
|
|
|
|
|
|
We have begun adding panel cutouts to the chassis 3D model for electrical,
|
|
|
optical, and structural connections to the ZCU216 and 16-channel RX board, and
|
|
|
for supplying power to the unit. Fiber connections for the RFoF downlink to the
|
|
|
16-channel RX board will be made on the front panel, with ethernet, power, and
|
|
|
other ZCU216 connections made through the back plate. An image of the chassis 3D
|
|
|
model with panel cutouts is shown below:
|
|
|
|
|
|
<div align="center">
|
|
|
<img src="../img/dbe/rfsoc-enclosure.png" width="500"/>
|
|
|
|
|
|
Figure: Utility Chassis 3D Model with Panel Cutouts
|
|
|
</div>
|
|
|
|
|
|
Physical dimensions of this chassis are given in the following table:
|
|
|
|
|
|
| Parameter | Specification |
|
|
|
| :------ | :------ |
|
|
|
| Overall Height | 5.22 in |
|
|
|
| Chassis Height | 4.75 in |
|
|
|
| Chassis Depth | 21.25 in |
|
|
|
| Overall Depth | 21.47 in |
|
|
|
|
|
|
Table: General Devices Item CHA-05-21, D-4001, Utility Chassis Dimensions
|
|
|
|
|
|
### 7.2.3 Power Requirements
|
|
|
The total power requirement for the ALPACA digital back end is expected to be
|
|
|
19.25kW. This includes all 25 servers and comprised hardware, 12 ZCU216
|
|
|
enclosures (supporting receiver electronics, fans, etc.), and 100GbE switch with
|
|
|
optics. It is proposed that each server rack have a dedicated 30 Amp 208VAC
|
|
|
supply. The following table shows the power requirements for the various systems
|
|
|
of the digital back end.
|
|
|
|
|
|
| Component | Consumption |
|
|
|
| :------ | :------ |
|
|
|
| AMD EPYC 7313 | 139W/155W (max) |
|
|
|
| Memory (8x16GB DDR4) | 22.4W |
|
|
|
| A10 GPU | 135W/150W (max) |
|
|
|
| MCX556-EDAT | 19.3W/26.8W (max) |
|
|
|
| 8 cm fan | 1.92W |
|
|
|
| SATA HDD | 6.5W (max) |
|
|
|
| SATA SSD | 2.2W (max) |
|
|
|
| 100GbE Switch | 1760W/1900W (max)|
|
|
|
| ZCU216 <br> w/ enclosure electronics| 130W |
|
|
|
| IB Switch | 75W/122.32W (max)
|
|
|
| data storage servers | 300W < P < 350W |
|
|
|
|
|
|
The expected total power requirement for the data storage hardware is 1.3kW.
|
|
|
This includes the three specified storage servers of [section
|
|
|
5.4](../5-dbe/5.4) and the IB switch with optics.
|
|
|
|
|
|
### 7.2.4 RFI Shielding
|
|
|
No regulatory EMI compatibility measurements or testing of the back end hardware
|
|
|
have been made. We anticipate however that the self-radiated RFI from both the
|
|
|
servers and the RFSoCs in their enclosures to be similar levels to each other,
|
|
|
typical for data centers, and as is common of other digital back ends found in
|
|
|
GBO facilities. We are expecting that the new GBO data center to be planned and
|
|
|
built to continue to accommodate non-RFI shielded computing hardware.
|
|
|
|
|
|
[Section 7.3 >>](./7.3)
|
|
|
|
|
|